Tyenaza ETCR2100A+

Tyenaza ETCR2100A+ Digital Clamp Resistance Tester User Manual

Model: ETCR2100A+

1. పరిచయం

This manual provides essential instructions for the safe and effective operation of the Tyenaza ETCR2100A+ Digital Clamp Resistance Tester. This device is designed for accurate measurement of grounding resistance and circuit resistance, featuring a dustproof and shockproof structure for reliable performance in various industrial and departmental settings.

Please read this manual thoroughly before using the instrument to ensure proper handling and to prevent damage or injury.

Tyenaza ETCR2100A+ Digital Clamp రెసిస్టెన్స్ టెస్టర్

Image 1.1: The Tyenaza ETCR2100A+ Digital Clamp Resistance Tester, showing its overall design with the clamp jaw and control panel.

2. భద్రతా సమాచారం

Always observe the following safety precautions to avoid electric shock, injury, or damage to the instrument:

  • Do not use the instrument if it appears damaged or is operating abnormally.
  • ఆపరేషన్ ముందు బ్యాటరీ కంపార్ట్‌మెంట్ సురక్షితంగా మూసివేయబడిందని నిర్ధారించుకోండి.
  • Do not attempt to measure live circuits beyond the specified voltage limits (CAT III 150V).
  • Avoid using the instrument in wet environments or during thunderstorms.
  • Refer to qualified personnel for any repairs or servicing.
  • Keep the instrument away from strong magnetic fields and electric fields exceeding specified limits.

3. ప్యాకేజీ విషయాలు

ప్యాకేజీలో అన్ని అంశాలు ఉన్నాయని నిర్ధారించుకోండి:

  • 1 x ETCR2100A+ Digital Clamp రెసిస్టెన్స్ టెస్టర్
  • 1 x Accessory (likely a test ring or similar calibration aid)
  • 1 x యూజర్ మాన్యువల్ (ఈ పత్రం)
  • 1 x నిల్వ పెట్టె

Note: 1.5V AA batteries (x4) are required and are not included in the package.

ETCR2100A+ Digital Clamp Resistance Tester with included accessory

Image 3.1: The ETCR2100A+ tester shown with a standard test ring, which is typically included as an accessory for calibration or verification.

4. ఉత్పత్తి లక్షణాలు

The ETCR2100A+ Digital Clamp Resistance Tester offers the following key features:

  • మల్టిఫంక్షనల్ డిస్ప్లే: Resistance and current values are displayed simultaneously on a new black luxury screen.
  • అధిక ఖచ్చితత్వం: Microprocessor-controlled for precise grounding resistance detection, utilizing fast filtering technology to minimize interference.
  • డేటా నిర్వహణ: Features real-time clock, data storage for up to 99 sets, and data retrieval capabilities.
  • వినగల మరియు దృశ్యమాన అలారం: "Beep beep beep" alarm sound with adjustable threshold settings for resistance (1-199 Ω) and current (1-499mA).
  • ఆటోమేటిక్ విధులు: Automatic shutdown and fully automatic gear shifting for ease of use.
  • బలమైన డిజైన్: Shockproof and dustproof structure, suitable for demanding industrial environments.
  • విస్తృత అప్లికేషన్: Ideal for telecommunications, power, meteorology, computer rooms, oil fields, power distribution lines, tower transmission lines, gas stations, factory grounding grids, and lightning rod systems.
క్లోజ్-అప్ view cl యొక్కamp jaws of the ETCR2100A+ tester

చిత్రం 4.1: క్లోజప్ view of the robust clamp jaws, highlighting the double insulation and structural features designed for durability and safety.

5. సెటప్

5.1 బ్యాటరీ ఇన్‌స్టాలేషన్

The ETCR2100A+ requires four (4) 1.5V AA batteries (not included).

  1. Locate the battery compartment cover on the back of the instrument.
  2. Use a suitable tool (if necessary) to open the battery compartment.
  3. Insert four 1.5V AA batteries, ensuring correct polarity (+/-) as indicated inside the compartment.
  4. బ్యాటరీ కంపార్ట్‌మెంట్ కవర్‌ను సురక్షితంగా మూసివేయండి.

5.2 ప్రారంభ పవర్ ఆన్

బ్యాటరీ ఇన్‌స్టాలేషన్ తర్వాత, నొక్కండి ఆన్/ఆఫ్ button to power on the device. The LCD display will illuminate, indicating the device is ready for use.

6. ఆపరేటింగ్ సూచనలు

6.1 ప్రాథమిక కొలత

To perform a grounding resistance test:

  1. పరికరం పవర్ ఆన్ చేయబడిందని నిర్ధారించుకోండి.
  2. cl తెరవండిamp ట్రిగ్గర్ నొక్కడం ద్వారా దవడలు.
  3. cl ఉంచండిamp around the grounding conductor or circuit to be measured. Ensure the jaws are fully closed around the conductor.
  4. The resistance value will be displayed on the LCD screen. The device features fully automatic shifting.
  5. The single measurement time is approximately 0.5 seconds.
ETCR2100A+ tester clamping an insulated ground wire

Image 6.1: The ETCR2100A+ tester shown clamping an insulated ground wire, demonstrating its capability to accurately test even insulated conductors.

6.2 Single Point Grounding System, Auxiliary Measurement

For single point grounding systems where direct clamp measurement of the lead wire is not feasible, auxiliary methods can be used. The two-point method is illustrated below:

Diagram illustrating the two-point auxiliary measurement method for single point grounding systems

Image 6.2: Diagram showing the two-point method for auxiliary grounding resistance measurement. It depicts a grounding rod (RA) connected to a single point, with a wire extending to a natural grounding point (e.g., water pipe, buried metal) for measurement.

ఈ పద్ధతిని ఉపయోగించడానికి:

  • Identify a natural grounding point with a low resistance value near the grounding point to be measured. Examples include a water pipe, fire hydrant, or other deeply buried metal structure.
  • Connect a wire from the point to be measured to this auxiliary grounding point.
  • Clamp the ETCR2100A+ around the connecting wire to perform the measurement.
ETCR2100A+ Digital Clamp Resistance Tester in an industrial substation environment

Image 6.3: The ETCR2100A+ tester positioned in an industrial substation, illustrating a typical application environment for grounding resistance measurement.

6.3 డేటా నిల్వ మరియు తిరిగి పొందడం

The instrument can store up to 99 sets of measurement data.

  • To store data: After a measurement, press the MEM button to save the current reading.
  • To retrieve data: Press the MEM button repeatedly to cycle through stored data.

6.4 అలారం ఫంక్షన్

The ETCR2100A+ features an audible and visual alarm for out-of-range measurements.

  • To activate/deactivate the alarm: Press the AL బటన్.
  • To set alarm thresholds: Refer to the device's on-screen menu or specific instructions for setting resistance (1-199 Ω) and current (1-499mA) alarm limits.
Hand holding the ETCR2100A+ Digital Clamp రెసిస్టెన్స్ టెస్టర్

Image 6.4: A hand holding the ETCR2100A+ tester, demonstrating its ergonomic design and ease of handling during operation.

7. నిర్వహణ

7.1 శుభ్రపరచడం

Wipe the instrument's exterior with a soft, damp cloth. Do not use abrasive cleaners or solvents. Ensure the device is powered off before cleaning.

7.2 నిల్వ

When not in use for extended periods, remove the batteries to prevent leakage. Store the instrument in its provided storage box in a cool, dry place, away from direct sunlight and extreme temperatures.

7.3 క్రమాంకనం

Regular calibration by qualified personnel is recommended to maintain measurement accuracy, especially after prolonged use or if accuracy is suspected to be compromised.

8. ట్రబుల్షూటింగ్

సమస్యసాధ్యమైన కారణంపరిష్కారం
పరికరం పవర్ ఆన్ చేయదు.డెడ్ లేదా తప్పుగా ఇన్‌స్టాల్ చేయబడిన బ్యాటరీలు.సరైన ధ్రువణతను నిర్ధారించుకోవడానికి, బ్యాటరీలను కొత్త 1.5V AA బ్యాటరీలతో భర్తీ చేయండి.
సరికాని రీడింగ్‌లు.Jaws not fully closed; interference from external fields; dirty jaws; need for calibration.Ensure jaws are fully closed. Move away from strong magnetic/electric fields. Clean jaws. Consider professional calibration.
అలారం నిరంతరం ధ్వనిస్తుంది.Measurement exceeds set alarm threshold.Check the measured value against the set alarm limits. Press the AL button to silence or deactivate the alarm.
డిస్ప్లే ఖాళీగా లేదా మినుకుమినుకుమంటోంది.Low battery power; environmental conditions (extreme temperature/humidity).Replace batteries. Operate within specified temperature and humidity ranges (-20 ℃ to 55 ℃; 10% RH to 90% RH).

9. స్పెసిఫికేషన్లు

మోడల్ETCR2100A+
ఫంక్షన్గ్రౌండింగ్ రెసిస్టెన్స్ టెస్ట్, సర్క్యూట్ రెసిస్టెన్స్ టెస్ట్, లీకేజ్ కరెంట్ టెస్ట్
ప్రతిఘటన పరిధి0.01 Ω నుండి 200 Ω వరకు
రెసిస్టెన్స్ రిజల్యూషన్0.001 Ω
ప్రస్తుత పరిధిNone (for leakage current test, the range is 1-499mA for alarm setting)
డేటా నిల్వ99 సెట్లు
Alarm Threshold Setting Range (Resistance)1-199 Ω
Alarm Threshold Setting Range (Current)1-499mA
పని ఉష్ణోగ్రత మరియు తేమ-20 ℃ to 55 ℃; 10% RH to 90% RH
LCD డిస్ప్లే4 digit LCD digital display
ప్రదర్శన పరిమాణంApprox. 47 x 28.5mm / 1.85 x 1.12in (L x W)
Jaw Size (Round)Approx. 32mm / 1.26in diameter
Jaw Opening Size (Long)సుమారు 32మి.మీ / 1.26అంగుళాలు
Clamp Size (Long Jaw)సుమారుగా 260 x 90 x 56మిమీ / 10.24 x 3.54 x 2.2అంగుళాలు
రక్షణ స్థాయిడబుల్ ఇన్సులేషన్
నిర్మాణ లక్షణాలుClamp shaped CT
గేర్ షిఫ్టింగ్Fully automatic shifting
బాహ్య అయస్కాంత క్షేత్రం<40A/m
బాహ్య విద్యుత్ క్షేత్రం<1V/m
Single Measurement Time0.5 సెకన్లు
Resistance Measurement FrequencyGreater than 1KHz
Tested Current Frequency50/60Hz automatic
విద్యుత్ సరఫరా4 x 1.5V AA బ్యాటరీలు (చేర్చబడలేదు)
మెటీరియల్ABS
వస్తువు బరువు2.13 కిలోలు / 4.69 పౌండ్లు

10. వారంటీ మరియు మద్దతు

వారంటీ సమాచారం, సాంకేతిక మద్దతు లేదా సేవా విచారణల కోసం, దయచేసి మీ రిటైలర్ లేదా తయారీదారుని నేరుగా సంప్రదించండి. కొనుగోలు రుజువుగా మీ కొనుగోలు రసీదును ఉంచండి.

Manufacturer: Tyenaza

© 2023 Tyenaza. All rights reserved.