1. పరిచయం

The Simplex 4090-9001 Individual Addressable Module (IAM) is a supervised device designed for use with Simplex IDNET fire alarm control panels. This module provides supervised monitoring of a normally open or normally closed contact, allowing the fire alarm system to monitor various external devices such as flow switches, tamper switches, or other alarm initiating devices. Its compact design and addressable capabilities ensure efficient and reliable integration into a comprehensive fire detection and alarm system.

This manual provides essential information for the proper installation, operation, and maintenance of the 4090-9001 IAM. Please read all instructions carefully before proceeding with installation or operation.

2. భద్రతా సమాచారం

Always adhere to local codes, ordinances, and regulations when installing and operating this device. Failure to do so may result in property damage, injury, or death. Only qualified personnel should install and service this equipment.

సాధారణ జాగ్రత్తలు:

Simplex 4090-9001 module with installation instructions sheet

Figure 2.1: Simplex 4090-9001 module shown with its installation instructions sheet, highlighting the importance of reviewing all documentation before installation.

3. సెటప్ మరియు ఇన్‌స్టాలేషన్

The 4090-9001 IAM is designed for easy installation within standard electrical boxes or compatible enclosures. Follow these steps for proper setup.

3.1 భౌతిక సంస్థాపన

  1. Mount the module in a suitable electrical box or enclosure, ensuring it is securely fastened. The module is designed for indoor dry applications.
  2. Ensure adequate space for wiring and ventilation around the module.

3.2 వైరింగ్ కనెక్షన్లు

Refer to the module's label and the specific installation instructions (part number 574-331 Rev G, as indicated on the module) for detailed wiring diagrams. The module features terminals for IDNET input/output and supervised contact connections.

Close-up of Simplex 4090-9001 module label showing wiring terminals

మూర్తి 3.1: ముందు view of the Simplex 4090-9001 module, clearly showing the IDNET input/output terminals (1-4) and the module's model number and revision information.

3.3 చిరునామా

The 4090-9001 is an addressable module. Its address is set electronically by the Simplex fire alarm control panel during system configuration. Refer to the control panel's programming manual for details on assigning and verifying module addresses.

4. ఆపరేషన్

The Simplex 4090-9001 IAM operates as an interface between a supervised initiating device circuit and the IDNET communication loop of a Simplex fire alarm control panel.

4.1 Supervised Monitoring

The module continuously monitors the connected contact circuit for changes in state (open or closed, depending on configuration) and for fault conditions (e.g., open circuit, short circuit) using an End-of-Line Resistor (EOLR). Upon detecting an alarm condition (e.g., contact closure for a flow switch) or a fault, the module communicates this status change to the fire alarm control panel via the IDNET loop.

5. నిర్వహణ

The Simplex 4090-9001 IAM is designed for reliable, long-term operation with minimal maintenance. However, periodic inspection and cleaning are recommended as part of a comprehensive fire alarm system maintenance program.

5.1 శుభ్రపరచడం

If the module accumulates dust or dirt, gently wipe the exterior with a soft, dry cloth. Do not use abrasive cleaners, solvents, or excessive moisture. Ensure the module is powered down before cleaning.

5.2 తనిఖీ

During routine system inspections, visually check the module for any signs of physical damage, loose connections, or environmental stress. Verify that the module's status indicator (if present) is operating normally according to the system's operational guidelines.

Simplex 4090-9001 module with UL listed label

మూర్తి 5.1: వైపు view of the Simplex 4090-9001 module, showing the UL Listed label, indicating compliance with safety standards.

6. ట్రబుల్షూటింగ్

This section provides guidance for common issues that may arise with the 4090-9001 IAM. For complex problems, contact a qualified Simplex service technician.

సమస్యసాధ్యమైన కారణంపరిష్కారం
Module not recognized by control panel.Incorrect wiring; Address not assigned or incorrect; Faulty module.Verify IDNET wiring (terminals 1-4). Check control panel programming for correct address assignment. Test module with a known good unit if possible.
Supervised circuit shows trouble.Open circuit; Short circuit; Incorrect EOLR; Faulty contact device.Check wiring for breaks or shorts. Verify correct EOLR value and installation. Test the connected contact device.
Module reports false alarms.Intermittent contact closure; Electrical noise; Faulty module.Inspect the connected device for intermittent operation. Check for sources of electrical interference. Consult Simplex technical support.

7. స్పెసిఫికేషన్లు

గుణంవివరాలు
బ్రాండ్సింప్లెక్స్
మోడల్ సంఖ్య4090-9001
ఉత్పత్తి కొలతలు9 x 4 x 8 అంగుళాలు
వస్తువు బరువు2.08 ఔన్సులు
శక్తి మూలంCorded Electric (via IDNET loop)
సెన్సార్ రకంPhotoelectric (refers to general fire alarm system components, not the module itself which monitors contacts)
అలారం రకంAudible (refers to general fire alarm system components, not the module itself which monitors contacts)
అప్లికేషన్Indoor Dry Application
అనుకూలతSimplex IDNET Fire Alarm Control Panels
UL లిస్టింగ్Fire Alarm Equipment Listed

8. వారంటీ సమాచారం

Simplex products are manufactured to high quality standards. For specific warranty terms and conditions, please refer to the warranty statement provided with your purchase or contact Simplex customer service. Keep your proof of purchase for warranty claims.

9. మద్దతు

For technical assistance, product inquiries, or service requests, please contact Simplex customer support or your authorized Simplex distributor. Provide the product model number (4090-9001) and any relevant system information when seeking support.

Manufacturer: Simplex

పార్ట్ నంబర్: 4090-9001

UPC: 753359764849

For additional resources and documentation, visit the official Simplex website or refer to the instruction manual 574-331 Rev G (if available digitally).

సంబంధిత పత్రాలు - 4090-9001

ముందుగాview సింప్లెక్స్ 4090-9007 IDNet సిగ్నల్ IAM: ఫైర్ అలారం సిస్టమ్స్ కోసం అడ్రస్సబుల్ మాడ్యూల్
సింప్లెక్స్ 4100ES, 4010ES, 4100U, మరియు 4008 సిరీస్ ఫైర్ అలారం కంట్రోల్ ప్యానెల్‌లలో మెరుగైన సెలెక్టివ్ సిగ్నలింగ్ మరియు ఆడియో నియంత్రణ కోసం రూపొందించబడిన సింప్లెక్స్ 4090-9007 IDNet సిగ్నల్ ఇండివిజువల్ అడ్రస్సబుల్ మాడ్యూల్ (IAM) కోసం వివరణాత్మక సాంకేతిక వివరణలు మరియు లక్షణాలు. వైరింగ్, ఆపరేషన్ మరియు మౌంటు సమాచారాన్ని కలిగి ఉంటుంది.
ముందుగాview సింప్లెక్స్ IDNet సిగ్నల్ IAM ఇన్‌స్టాలేషన్ సూచనలు
సింప్లెక్స్ 4090-9007 IDNet అడ్రస్సబుల్ సిగ్నల్ ఇండివిజువల్ అడాప్టర్ మాడ్యూల్ (సిగ్నల్ IAM) కోసం వివరణాత్మక ఇన్‌స్టాలేషన్ సూచనలు, చిరునామా సెట్టింగ్, క్లాస్ A మరియు క్లాస్ B నోటిఫికేషన్ అప్లయన్స్ సర్క్యూట్‌ల (NACలు) కోసం వైరింగ్ కాన్ఫిగరేషన్‌లు మరియు మౌంటు విధానాలను కవర్ చేస్తాయి. ఈ గైడ్ సిగ్నల్ IAMని ఫైర్ అలారం కంట్రోల్ ప్యానెల్‌లు మరియు నోటిఫికేషన్ ఉపకరణాలతో అనుసంధానించడానికి అవసరమైన సమాచారాన్ని అందిస్తుంది.
ముందుగాview మాడ్యులో డైరెసియోనబుల్ ఇండివిజువల్ సింప్లెక్స్ 4090-9007 IAM డి సెనల్ పారా ప్యానెల్స్ డి అలార్మా డి ఇన్సెండియోస్
Descubra el Módulo Direccionable Individual (IAM) de Señal Simplex 4090-9007, un periférico IDNet para paneles de control de alarma de incendios 4007ES, 4008, 4010ES, 4100ES y 4100U. Proporciona señalización selectiva, supervisión de NAC, control de audio y cumple con UL, ULC, CSFM y FM.
ముందుగాview Módulo Endereçável ఇండివిజువల్ సింప్లెక్స్ 4090-9007 IDNet పారా సినాలిజాకో డి అలార్మే డి ఇంకెండియో
Este documento técnico detalha o Módulo Endereçável Individual (IAM) Simplex 4090-9007 IDNet, projetado para fornecer sinalização adicional em painéis de controle de alarme de incêndio Simplex séries 4007ES, 4008, 4010ES, 4100ES e 4100U. Inclui características, recursos de supervisão, detalhes de operação, especificações elétricas e mecânicas, requisitos de fiação e informações de montagem para otimização de sistemas de alarme de incêndio.
ముందుగాview సింప్లెక్స్ 4090-9101, 4090-9106 మానిటర్ ZAM ఇన్‌స్టాలేషన్ సూచనలు
సింప్లెక్స్ 4090-9101 మరియు 4090-9106 మానిటర్ జోన్ అడాప్టర్ మాడ్యూల్స్ (ZAMలు) కోసం ఇన్‌స్టాలేషన్ సూచనలు. IDNet మరియు MAPNET II సిస్టమ్‌ల కోసం మెకానికల్ ఇన్‌స్టాలేషన్, DIP స్విచ్‌ల ద్వారా అడ్రస్ సెట్టింగ్ మరియు ఎలక్ట్రికల్ కనెక్షన్‌లను కవర్ చేస్తుంది.
ముందుగాview సింప్లెక్స్ 4010ES: సిస్టమ్స్ డి కమాండే డి'ఎక్స్‌టింక్షన్ ఆటోమేటిక్ పోర్ గిక్లర్స్
గైడ్ టెక్నిక్ సింప్లెక్స్ 4010ES డిటైలెంట్ లెస్ మాడ్యూల్స్ డి కమాండే పోర్ లెస్ సిస్టమ్స్ డి'ఎక్స్‌టింక్షన్ ఆటోమేటిక్ పార్ గిక్లెర్స్, కౌవ్రాంట్ లెస్ మోడ్‌లు డెల్యూజ్ మరియు ప్రెవెంటిఫ్, అవెక్ స్పెసిఫికేషన్స్, హోమోలోగేషన్స్ మరియు స్కీమాస్ డి సిబ్లేజ్.