ABB SACE E2.2H-A

ABB SACE EMAX2 E2.2 H 1600 Ekip Touch LSIG 3p WMP యూజర్ మాన్యువల్

Model: SACE E2.2H-A | Brand: ABB

1. పరిచయం మరియు ఉత్పత్తి ముగిసిందిview

This manual provides essential information for the safe and effective installation, operation, and maintenance of the ABB SACE EMAX2 E2.2 H 1600 Ekip Touch LSIG 3p WMP Air Circuit Breaker. Please read this manual thoroughly before any operation.

The ABB SACE EMAX2 E2.2H 1600 is a fixed three-pole air circuit breaker equipped with rear horizontal terminals and a solid-state release in AC EKIP/DIP-LI R 1600. It includes four auxiliary contacts and a circuit breaker in the open-closed position.

ముఖ్య లక్షణాలు:

  • Mounting type: Plug-In Mount
  • వాల్యూమ్tage: 600.0 volts of alternating current
  • Circuit breaker type: Standard
  • ప్రస్తుత రేటింగ్: 1600.0 amps
  • ధ్రువాల సంఖ్య: 3
ముందు view of the ABB SACE EMAX2 E2.2 H 1600 Air Circuit Breaker

మూర్తి 1: ముందు view of the ABB SACE EMAX2 E2.2 H 1600 Air Circuit Breaker, showing the Ekip Touch display, operating buttons (OPEN, Push OFF, Push ON), and the reset mechanism.

2. సెటప్ మరియు ఇన్‌స్టాలేషన్

The ABB SACE EMAX2 E2.2 H 1600 is designed for plug-in mounting. Proper installation by qualified personnel is crucial for safety and optimal performance.

2.1 అన్‌ప్యాకింగ్ మరియు తనిఖీ

Carefully unpack the circuit breaker and all accessories. Inspect for any signs of shipping damage. Ensure all components listed in the packing slip are present.

ABB SACE EMAX2 E2.2 H 1600 Air Circuit Breaker inside its wooden shipping crate

Figure 2: The circuit breaker securely packed within its wooden shipping crate, indicating careful handling during transport.

Accessories for the ABB SACE EMAX2 E2.2 H 1600 Air Circuit Breaker, including mounting hardware and documentation, in clear plastic bags

Figure 3: Various accessories, such as mounting brackets and additional components, packaged separately for the circuit breaker.

2.2 మౌంటు

This unit features a plug-in mount design. Refer to the detailed installation diagrams and instructions provided with the product for specific mounting procedures. Ensure the mounting surface is stable and capable of supporting the unit's weight (approximately 105.82 pounds).

2.3 విద్యుత్ కనెక్షన్లు

Connect the main power lines to the designated terminals. The unit is a three-pole breaker. Ensure all connections are secure and comply with local electrical codes and standards.

టాప్ view of the ABB SACE EMAX2 E2.2 H 1600 Air Circuit Breaker showing the three main connection points with copper busbars

మూర్తి 4: టాప్ view illustrating the three main connection points for electrical wiring, designed for robust and secure connections.

Warning: All electrical work must be performed by a qualified electrician. Disconnect all power before installation or maintenance.

3. ఆపరేటింగ్ సూచనలు

The ABB SACE EMAX2 E2.2 H 1600 features an Ekip Touch interface and mechanical push buttons for operation.

3.1 ప్రాథమిక ఆపరేషన్

  • To Close (Turn On): Press the "Push ON" button (green). The breaker will close, allowing current flow.
  • To Open (Turn Off): Press the "Push OFF" button (red). The breaker will open, interrupting current flow.
  • ఎమర్జెన్సీ ఓపెన్: Use the "OPEN" lever for immediate manual opening.
  • రీసెట్: After a trip event, identify and resolve the cause. Then, press the "Reset" button to reset the tripping mechanism before attempting to close the breaker again.
Close-up of the operating panel of the ABB SACE EMAX2 E2.2 H 1600, showing the 'OPEN' lever, 'Push OFF' (red), 'Push ON' (green) buttons, and 'Reset' button.

మూర్తి 5: వివరంగా view of the operational controls, including the Ekip Touch display and the mechanical buttons for opening, closing, and resetting the breaker.

3.2 Ekip Touch Interface

The Ekip Touch display provides real-time data, settings, and diagnostic information. Refer to the separate Ekip Touch user guide for detailed navigation and configuration instructions.

4. నిర్వహణ

Regular maintenance ensures the longevity and reliable operation of your ABB SACE EMAX2 circuit breaker. Always disconnect power before performing any maintenance.

4.1 దినచర్య తనిఖీలు

  • Visually inspect the breaker for any signs of damage, loose connections, or excessive dust accumulation.
  • వెంటిలేషన్ ఓపెనింగ్‌లు స్పష్టంగా మరియు అడ్డంకులు లేకుండా ఉన్నాయని నిర్ధారించుకోండి.
  • Check the integrity of all wiring and terminal connections.

4.2 శుభ్రపరచడం

Use a dry, lint-free cloth to clean the exterior surfaces. Do not use abrasive cleaners or solvents. For internal cleaning, consult a qualified service technician.

వైపు view of the ABB SACE EMAX2 E2.2 H 1600 Air Circuit Breaker, showing internal mechanical components and gear assembly

మూర్తి 6: వైపు view revealing the intricate mechanical components and gear assembly responsible for the breaker's operation, highlighting areas that may require professional inspection.

4.3 ప్రొఫెషనల్ సర్వీసింగ్

Periodic professional servicing by ABB-certified technicians is recommended to ensure optimal performance and compliance with safety standards. This includes checking internal mechanisms and calibration of the Ekip Touch unit.

5. ట్రబుల్షూటింగ్

This section provides general guidance for common issues. For complex problems, contact ABB technical support or a qualified electrician.

5.1 తరచుగా బ్రేకర్ ట్రిప్పులు

  • ఓవర్‌లోడ్: Check the connected load. Reduce the load if it exceeds the breaker's rated current (1600 A).
  • షార్ట్ సర్క్యూట్: Inspect wiring for short circuits. This requires immediate attention and professional diagnosis.
  • గ్రౌండ్ ఫాల్ట్: If applicable, check for ground faults in the system.
  • తప్పు పరికరాలు: Disconnect individual equipment to identify a faulty device causing the trip.

5.2 Breaker Does Not Close

  • పడిపోయిన స్థితి: Ensure the breaker is fully reset after a trip. The "DISCHARGED SPRING" indicator might be visible if not reset.
  • శక్తి లేదు: Verify incoming power supply.
  • Mechanical Obstruction: Check for any physical obstructions preventing the mechanism from closing.
Close-up of the product label on the ABB SACE EMAX2 E2.2 H 1600 Air Circuit Breaker, showing model SACE E2.2H-A, serial number, ratings, and UL Listed certification.

Figure 7: Product label providing critical specifications such as model number (SACE E2.2H-A), serial number, rated maximum voltage, rated short-circuit current, and UL/CSA certifications.

6. స్పెసిఫికేషన్లు

Detailed technical specifications for the ABB SACE EMAX2 E2.2 H 1600 Ekip Touch LSIG 3p WMP Air Circuit Breaker:

స్పెసిఫికేషన్విలువ
Product Main TypeSACE Emax 2
మోడల్ సంఖ్యSACE E2.2H-A
రేట్ చేయబడిన ప్రస్తుత (లో)1600 ఎ
పోల్స్ సంఖ్య3
ప్రస్తుత రకంAC
వాల్యూమ్ రేట్ చేయబడిందిtagయూరో)690 వి
రేట్ చేయబడిన కార్యాచరణ వాల్యూమ్tage690 V AC
రేట్ చేయబడిన ఇన్సులేషన్ వాల్యూమ్tagఇ (Ui)ఎసి 1000 వి
రేట్ చేయబడిన ఇంపల్స్ తట్టుకునే వాల్యూమ్tagఇ (Uimp)12 kV (acc. to IEC 60947-2)
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(400 V AC) 100 kA, (415 V AC) 100 kA, (440 V AC) 100 kA, (500 V AC) 85 kA, (525 V AC) 85 kA, (690 V AC) 85 kA
Rated Service Short-Circuit Breaking Capacity (Ics)(220 V AC) 100 kA, (230 V AC) 100 kA, (380 V AC) 100 kA, (400 V AC) 100 kA, (415 V AC) 100 kA, (440 V AC) 100 kA, (500 V AC) 85 kA, (660 V AC) 85 kA, (690 V AC) 85 kA
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics)100 %
రేట్ చేయబడిన స్వల్పకాలిక తట్టుకునే ప్రస్తుత తక్కువ వాల్యూమ్tagఇ (ఐసిడబ్ల్యు)for 1 s 85 kA, for 3 s 66 kA
Rated Uninterrupted Current (Iu)1600 ఎ
విద్యుత్ మన్నికUe =<440 V 12000 cycle, Ue = 500 ... 690 V 10000 cycle (30 cycles per hour)
మెకానికల్ మన్నిక25000 cycle (60 cycles per hour)
శక్తి నష్టం288 W
ఉత్పత్తి కొలతలు15.08 x 12.48 x 16.73 అంగుళాలు
బరువు105.82 పౌండ్లు
మూలం దేశంఇటలీ

Note: Specifications are subject to change without notice. Always refer to the product label and official ABB documentation for the most accurate and up-to-date information.

Shipping label for ABB SACE EMAX2 E2.2 H 1600, showing product version, poles, overcurrent release type, and a barcode with the number 8057558336022.

Figure 8: Product identification label, including the EAN/UPC code 8057558336022, which can be used for product verification and lookup.

7. వారంటీ మరియు మద్దతు

For warranty information and technical support, please refer to the official ABB documentation included with your product or visit the official ABB webసైట్.

  • రిటర్న్స్: This product is eligible for 30-day easy returns. Please check the retailer's return policy for details.
  • కస్టమర్ మద్దతు: For assistance, contact customer support through your purchase platform or directly via ABB's official channels.
  • ABB Store: You can find more information and products from ABB by visiting the official ABB Store.

సంబంధిత పత్రాలు - SACE E2.2H-A

ముందుగాview ABB SACE Emax 2: New Low Voltage Air Circuit-Breakers Technical Catalogue
Explore the ABB SACE Emax 2 series of new low voltage air circuit-breakers. This technical catalogue provides detailed information on features, ranges, protection trip units, communication, accessories, and specifications for efficient power management and system reliability.
ముందుగాview ABB SACE Emax 2 Low Voltage Air Circuit-Breakers Technical Catalogue
Comprehensive technical catalogue detailing ABB's SACE Emax 2 series of low voltage air circuit-breakers, covering features, specifications, protection, connectivity, and accessories for advanced electrical distribution systems.
ముందుగాview ABB SACE Tmax XT Catalog: Low Voltage Molded Case Circuit-Breakers
Explore the ABB SACE Tmax XT series, a cutting-edge range of low voltage molded case circuit-breakers offering advanced performance, connectivity, ease of use, and robust protection for diverse industrial and commercial applications.
ముందుగాview ABB SACE Emax 2 ఎయిర్ సర్క్యూట్-బ్రేకర్లు: ఆపరేటింగ్ సూచనలు
ABB SACE Emax 2 తక్కువ వాల్యూమ్ కోసం సమగ్ర ఆపరేటింగ్ సూచనలుtage ఎయిర్ సర్క్యూట్-బ్రేకర్లు, ఉత్పత్తి ఎంపిక, ట్రిప్ యూనిట్ విధులు, ఉపకరణాలు మరియు డిజైన్ ఇంజనీర్ల కోసం సాంకేతిక వివరణలను కవర్ చేస్తాయి.
ముందుగాview ABB Electrical Installation Handbook: Protection, Control, and Electrical Devices
Comprehensive technical guide from ABB covering electrical installation, protection, control devices, circuit breakers, switch disconnectors, and relevant standards. Features detailed specifications and coordination tables.
ముందుగాview SACE Tmax XT Circuit Breaker Installation Guide
Comprehensive installation instructions and recommended conditions for ABB SACE Tmax XT circuit breakers, covering AC and DC applications, wiring diagrams, dimensional data, and trip test procedures.